Fire Proof Doors

A fire door is a door with a fire resistance rating sometimes referred to as a fire protection rating for closures) used as part of a passive fire protection system to reduce the rate of spread of fire or smoke. between compartments to enable safe egress from a hazardous building or structure.

They are wooden and steel doors.

Combustibility

Fire doors are not necessarily noncombustible. It is acceptable for portions of the door to be destroyed by combustion during exposure to a fire as long as the door assembly meets the fire test criteria of limiting temperature limits on the non-fire side of the assembly. This is in accordance with the overall performance goal of a fire rated door to slow fire propagation from one fire rated compartment to another for only a limited amount of time, during which automatic or manual fire fighting may be employed to limit fire spread, or occupants can exit the building.

Normal operation

Most fire doors are designed to be kept closed at all times. Some doors are designed to stay open under normal circumstances, and close automatically in the event of a fire. Whichever method is used, the door's movement should never be impaired by a doorstop or other obstacle. The intumescent and smoke-seal bounding of fire doors should be routinely checked, as should the action of the door closer and latch.

Some fire doors are held open with an electromagnet, which may be wired to a fire alarm system. If the power fails or the fire alarm is activated, the coil is de-energized and the door closes on its own.

Rated fire doors are tested to withstand a fire for a specified period. There are 20, 30, 45, 60 and 90-minute-rated fire doors that are certified by an approved laboratory (e.g. Under writers laboratories) The certification only applies if all parts of the installation are correctly specified and installed. For example, fitting the wrong kind of glazing may severely reduce the door's fire resistance period.

Installation

As well as ensuring the door is hung properly and squarely, it is also very important that where a fire door is installed, any gaps left in the opening between the wall and the door frame must be properly filled with fire resisting material. Fire doors are normally installed by a carpenter

  1. No Open Holes or breaks exist in surfaces of either the door or frame.
  2. Glazing, vision light frames & glazing beads are intact and securely fastened in place, if so equipped.
  3. The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible signes of damage.
  4. No parts are missing or broken.
  5. Door clearances at the door edge of the door frame, on the pull side of the door, do not exceed clearances listed in 4.8.4 (the clearance under the bottom of the door shall be a maximum of 3/4") and 6.3.1 (top & edges 1/8")
  6. The self-closing device is operational; that is, the active door completely closes when operated from the full open position.
  7. If a coordinator is installed, the inactive leaf closes before the active leaf.
  8. Latching hardware operates and secure the door when it is in the closed position.
  9. Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.
  10. No field modifications to the door assembly have been performed that void the label.
  11. Gasketing and edge seals, where required, are inspected to verify their presence and integrity.